DWA01CM235A CARLO GAVAZZI Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIAB.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DWA01CM235A CARLO GAVAZZI Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIAB..

DWA01CM235A

DWA01CM235A

CARLO GAVAZZI

Available

Ship on today

Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE Power and power factor monitoring Others SIZE 22,5 mm POWER SUPPLY RANGE 208÷240 VAC MONITORING FUNCTION PF monitoring MOUTING DIN-rail INPUT RANGE 0.1-0.99

More details


Energy Meters Control Analizers

Controls

Monitoring Relays and Measurement Current Transformers

* Brand new produt in its original packing covered by the warranties and certifications provided by CARLO GAVAZZI

QuantityPrice
1+$130.84
2+$127.24
4+$124.32
5+$123.50
7+$122.85
*This price is per unit and is the net value (not including taxes if applicable).

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Monitoring Relays
3-Phase LoadGuard
Types DWA01, PWA01
DWA01PWA01
• Cos ϕ monitoring relays
• Measuring if power factor is within set limits
• Measure their own power supply (voltage) and current for balanced systems
• Measuring ranges for current: 5A and MI current transformers range
• Power ON delay 1, 2 or 6 s selectable
• Knob adjustable level on absolute scale
• Output: 8 A SPDT relay Normally Energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DWA01) or plug-in module (PWA01)
• 22.5 mm Euronorm housing (DWA01) or 36 mm plug-in module (PWA01)
• LED indication for power supply and output ON
Product Description Ordering key
DWA01 C M48 5A
DWA01 and PWA01 are pre- cise over or under cos ϕ monitoring relays.
The relays monitor their own powersupplyvoltageand the current of a balanced 3- phase system.
Forcurrentmeasure direct connection, 5A standard current transformers and MI CT can be used.
The LED's indicate the state of the alarm and the output relay.
Housing Function Type
Item number
Output
Power Supply
Range
Type Selection
MountingOutputSupply: 208 to 240 VAC Supply: 380 to 415 VAC Supply: 380 to 480 VAC
DIN-railSPDTDWA 01 C M23 5A DWA 01 C M48 5A
Plug-in SPDTPWA 01 C M23 5APWA 01 C M48 5A
InputSpecifications
Input
Voltage (Own power supply):
Measuring ranges
Level
3 - phaseDWA01: L1, L2, L3
PWA01: 5, 6, 7
M23: 208 to 240 VAC ± 15% DWA01CM48: 380 to 480 VAC ± 15% PWA01CM48: 380 to 415 VAC ± 15%
1- phaseDWA01CM235A: L1, L3
PWA01CM235A: 5, 7
208 to 240 VAC ± 15% Current DWA01: 5A: L1, I2
MI CT: U1, U3
PWA01: 5A: 9, 10
MI CT: 8, 11
Power factor (cos ϕ) 0.1 to 0.99
AACrmsMax. curr.
Direct input 0.5 to 5 A 30A 30s
Standard CT (examples)
TADK 2 50 A/5 A 5 to 50 A60 A CTD1 150 A/5 A15 to 150 A180 A CTD4 400 A/5 A40 to 400 A480 A TAD12 1000 A/5 A100 to 1000 A1200 A TACO200 6000 A/5 A600 to 6000 A7200 A
MI CT ranges
MI 100 10 to 100 A250 AAC MI 500 50 to 500 A750 AAC
Note:
The input voltage cannot raise over 300 VAC with respect to ground (PWA01 only).
Hysteresis~ cos ϕ = 0,02 - fixed
Specifications are subject to change without notice (23.11.10)1

Datasheet - PDF

Title:Language:Size:Type:
pdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE P - CARLO GAEnglish191 Kbytespdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE P - CARLO GA
pdf1-Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE P - CARLO English12 Mbytespdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE P - CARLO GA
pdf2-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE P - CARLO GAEnglish630 Kbytespdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE P - CARLO GA

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review