UA75-30-00RA 1SBL411024R8400 ABB UA75-30-00RA 110V 50Hz / 110-120V 60Hz Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UA75-30-00RA 1SBL411024R8400 ABB UA75-30-00RA 110V 50Hz / 110-120V 60Hz Contactor

UA75-30-00RA

1SBL411024R8400

ABB

Available

Ship on today

UA75-30-00RA 110V 50Hz / 110-120V 60Hz Contactor

More details


Contactor Relays

Contactors and overload relays

Contactors "A" FRCTLP

* Brand new produt in its original packing covered by the warranties and certifications provided by ABB

QuantityPrice
1+$275.84
2+$269.97
3+$269.03
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



UA75..RA 3-pole contactors for capacitor switching, can be used in installations in which the peak current far exceeds 100 times nominal rms current. The contactors are delivered complete with their damping resistors and must be used without additional inductances (see table below). The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are making. Their electrical durability is 250 000 operating cycles for Ue < 500 V and 100 000 operating cycles for 500 V ≤ Ue ≤ 690 V. The UA..RA contactors are fitted with a special front mounted block, which ensures the serial insertion of 3 damping resistors into the circuit to limit the current peak on energization of the capacitor bank. Their connection also ensures capacitor precharging in order to limit the second current peak occurring upon making of the main poles. The insertion of resistors allows to damp the highest current peak of the capacitor when switching on, whatever its level. The UA..RA series 3-pole contactors are of the block type design. - Main poles: 3 main poles - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.

Ordering

  • EAN:
    3471522305848
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85369085

Dimensions

  • Product Net Width:
    70 mm
  • Product Net Depth:
    140.4 mm
  • Product Net Height:
    150 mm
  • Product Net Weight:
    1.350 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    160 mm
  • Package Level 1 Length:
    200 mm
  • Package Level 1 Height:
    85 mm
  • Package Level 1 Gross Weight:
    1.35 kg
  • Package Level 1 EAN:
    3471522305848
  • Package Level 2 Units:
    63 piece

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    0
  • Number of Auxiliary Contacts NC:
    0
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Short-Circuit Protective Devices:
    gG Type Fuses 200 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
  • Maximum Electrical Switching Frequency:
    240 cycles per hour
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to UL/CSA 600 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1)0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
  • Rated Control Circuit Voltage (Uc):
    50 Hz 110 V
    60 Hz 110 … 120 V
  • Coil Consumption:
    Average Holding Value 50 / 60 Hz 18 V·A
    Average Holding Value 50 / 60 Hz 5.5 W
    Average Holding Value 50 Hz 18 V·A
    Average Holding Value 50 Hz 5.5 W
    Average Holding Value 60 Hz 18 V·A
    Average Holding Value 60 Hz 5.5 W
    Average Pull-in Value 50 Hz 180 V·A
    Average Pull-in Value 60 Hz 210 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 8 ... 27 ms
    Between Coil De-energization and NO Contact Opening 4 ... 11 ms
  • Connecting Capacity-Main Circuit:
    Rigid Cable6 ... 16 mm²
    Flexible with Cable End6 ... 10 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Rigid Cable1 ... 4 mm²
    Flexible with Cable End0.75 ... 2.5 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
  • Connecting terminals (delivered in open position) Main poles:
    M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C
    Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C
    Close to Contactor for Storage -60 ... +80 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible:
    3000 m
  • RoHS Status:
    No declaration needed

Certificates and Declarations (Document Number)

Classifications

  • ETIM 5:
    EC001079 - Capacitor magnet contactor
  • UNSPSC:
    39121529

Datasheet - PDF

Title:Language:Size:Type:
pdf-UA75-30-00RA 110V 50Hz / 110-120V 60Hz Contactor - ABB - UA75-30-00RA - 1SBL411024R8400English96 Kbytespdf-UA75-30-00RA 110V 50Hz / 110-120V 60Hz Contactor - ABB - UA75-30-00RA - 1SBL411024R8400

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or