AF116-30-00B-11 1SFL427002R1100 ABB AF116-30-00B-11 Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

AF116-30-00B-11 1SFL427002R1100 ABB AF116-30-00B-11 Contactor

AF116-30-00B-11

1SFL427002R1100

ABB

Available

Ship on today

AF116-30-00B-11 Contactor

More details


Contactor Relays

Contactors and overload relays

AF contactors 100A to 370A

* Brand new produt in its original packing covered by the warranties and certifications provided by ABB

QuantityPrice
1+$350.91
2+$344.94
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V. Operated with wide control voltage range 24-60 V, 50 and 60 Hz, 20-60 V DC

Ordering

  • EAN:
    7320500476499
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Dimensions

  • Product Net Width:
    90.0 mm
  • Product Net Depth:
    126.0 mm
  • Product Net Height:
    150.0 mm
  • Product Net Weight:
    1.512 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    194 mm
  • Package Level 1 Length:
    115 mm
  • Package Level 1 Height:
    169 mm
  • Package Level 1 Gross Weight:
    1.642 kg
  • Package Level 1 EAN:
    7320500476499

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    0
  • Number of Auxiliary Contacts NC:
    0
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Rated Frequency (f):
    Main Circuit 50/60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 55 °C 145 A
    (690 V) 40 °C 160 A
    (690 V) 70 °C 130 A
  • Rated Operational Current AC-3 (Ie):
    (690 V) 55 °C 65 A
    (220 / 230 / 240 V) 55 °C 116 A
    (415 V) 55 °C 116 A
    (440 V) 55 °C 116 A
    (380 / 400 V) 55 °C 116 A
    (500 V) 55 °C 110 A
  • Rated Operational Power AC-3 (Pe):
    (500 V) 75 kW
    (220 / 230 / 240 V) 30 kW
    (690 V) 55 kW
    (380 / 400 V) 55 kW
    (440 V) 75 kW
    (415 V) 55 kW
  • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
    8 x Ie AC-3
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Short-Circuit Protective Devices:
    gG Type Fuses 250 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A
  • Maximum Electrical Switching Frequency:
    AC-3 300 cycles per hour
    AC-1 300 cycles per hour
    AC-2 / AC-4 150 cycles per hour
  • Rated Operational Current DC-1 (Ie):
    (110 V) 2 Poles in Series, 40 °C 145 A
    (220 V) 3 Poles in Series, 40 °C 145 A
  • Rated Operational Current DC-3 (Ie):
    (110 V) 2 Poles in Series, 40 °C 145 A
    (220 V) 3 Poles in Series, 40 °C 145 A
  • Rated Operational Current DC-5 (Ie):
    (110 V) 2 Poles in Series, 40 °C 145 A
    (220 V) 3 Poles in Series, 40 °C 145 A
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):
    Main Circuit 8 kV
  • Mechanical Durability:
    5 million
  • Maximum Mechanical Switching Frequency:
    300 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1)0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
  • Rated Control Circuit Voltage (Uc):
    60 Hz 24…60 V
    50 Hz 24…60 V
    DC Operation 20…60 V
  • Coil Consumption:
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·A
    Holding at Max. Rated Control Circuit Voltage DC 2.5 W
    Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·A
    Pull-in at Max. Rated Control Circuit Voltage DC 210 W
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·A
    Holding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 25…55 ms
    Between Coil De-energization and NO Contact Opening 37…47 ms
  • Connecting Capacity-Main Circuit:
    Flexible 2x10…70 mm²
    Rigid Cu-Cable 2x10…95 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Solid 2x1…4 mm²
    Flexible with Insulated Ferrule 2x0.75…2.5 mm²
    Stranded 1x1…4 mm²
    Flexible 2x0.75…2.5 mm²
    Flexible with Ferrule 1x0.75…2.5 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
  • Terminal Type:
    Main Circuit: Bars

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
    Close to Contactor for Storage -40…+70 °C
  • Maximum Operating Altitude Permissible:
    3000 m
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Main Circuit 600 V
  • General Use Rating UL/CSA:
    (600 V AC) 160 A
  • Horsepower Rating UL/CSA:
    (208 V AC) Three Phase 30 Hp
    (440 ... 480 V AC) Three Phase 75 Hp
    (550 ... 600 V AC) Three Phase 100 Hp
    (220 ... 240 V AC) Three Phase 40 Hp
    (200 V AC) Three Phase 30 Hp

Certificates and Declarations (Document Number)

Classifications

  • ETIM 5:
    EC000066 - Magnet contactor, AC-switching
  • UNSPSC:
    39121529

Datasheet - PDF

Title:Language:Size:Type:
pdf-AF116-30-00B-11 Contactor - ABB - AF116-30-00B-11 - 1SFL427002R1100English96 Kbytespdf-AF116-30-00B-11 Contactor - ABB - AF116-30-00B-11 - 1SFL427002R1100

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or